Final | 9/7/2007 | 9/10/2007 | 9/10/2007 | A | PASS |
Bob Reichert
|
|
|
This will be for a final on this job. Justin Metcalf is the contact. Thank you very much Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called contr, left message for 2 recpts with open grounds, met owner told to let know if contr didn't fix, survey, ok to final
|
Electrical Rough-In | 8/6/2007 | 8/6/2007 | 8/6/2007 | P | PASS |
Bob Reichert
|
|
|
steve Phone #: ###-#### corr made, ric ok
|
Electrical Rough-In | 8/1/2007 | 8/1/2007 | 8/1/2007 | P | FAIL |
Bob Reichert
|
|
|
Contact Steve Berry with any problems or questions on the Rough in. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) recpts shall be installed such that no point along wall space is over 6' from an outlet, 314.20 in walls of combustible material, box shall be flush with finished surface
|
Application received | | | 8/1/2007 | | |
|
|
|
|
Issue permit | | | 8/1/2007 | | DONE |
|
|
|
|