Second Notice ELE | 10/12/2007 | 10/12/2007 | 10/19/2007 | | DONE |
|
|
|
This permit finaled on the web by Todd Holbrook
|
First Notice | 9/20/2007 | 9/20/2007 | 10/12/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | PASS |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook ok no card
|
Final | 9/20/2007 | 9/20/2007 | 9/20/2007 | A | PART |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook met elect, need to fix kitchen gfci, install floor recpt, strap a/c flex, wire drinking fountain, relocate fixture over kitchen sink, rest ok
|
Permanent Service | 8/22/2007 | 8/22/2007 | 8/22/2007 | P | PASS |
Bob Reichert
|
|
|
chris Phone #: ###-#### called, left message to move plant in front of service, p/s u/g n ok
|
Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 | A | PASS |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called contr about ent protection, rest corrections made, ric hard lids and walls ok
|
Electrical Rough-In | 8/2/2007 | 8/3/2007 | 8/3/2007 | A | FAIL |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and raceways shall be 1/14" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of term point, 110.26(F)(1) there shall be no foreign systems in dedicated electrical space over panel, 300.5 u/g shall be covered with minimum 2" concrete
|
Application received | | | 8/2/2007 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|