Telephone call | | | 12/20/2007 | | DONE |
|
|
|
tlk to brad the final was only 12068 the remaining amount was LCCM amount that the landlord did not him 8:55
|
Telephone call | | | 12/19/2007 | | DONE |
|
|
|
lft vm with multi state to verify he final value 11:55
|
First Notice | 8/30/2007 | 8/30/2007 | 9/10/2007 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by Brad Baker
|
Final | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | PASS |
Jack Frank
|
|
|
ready for final on this project (Plato''s)please call if any questions thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker ok card signed
|
Electrical Rough-In | 8/6/2007 | 8/6/2007 | 8/6/2007 | P | PASS |
Bob Reichert
|
|
|
please make the inspection 1st thing this afternoon thank you Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker ri walls and ceiling ok to cover
|
Electrical Rough-In | 8/2/2007 | 8/3/2007 | 8/3/2007 | P | FAIL |
Bob Reichert
|
|
|
call for answers (not much to inspect)thanks Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker called, left message, left corr notice, nec 300.11 tie wires required for all fixtures, 330.30(B) &348.30(A) mc and fmc shall be secured within 12" of term point, 300.11(A) cables shall not be supported by grid, 725.3(B) lv cables that are abandoned shall be removed, BCC no violations shall be retained, blank off recpt in ceiling cavity
|
Owner Supplied Equipment | | | 8/2/2007 | | |
|
|
|
|
Application received | | | 8/2/2007 | | DONE |
|
|
|
This permit was created on the web by Brad Baker
|