complete wiring for 8,128 sq ft office bld with shell (shell and core area) - $63,489 per initial cert of value ///final value is $64,597.00 per faxed document 12-7-07ps
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE12/4/200712/4/200712/7/2007 DONE
First Notice has not been responded to.
First Notice11/15/200711/15/200712/4/2007 DONE
DetailsMike Kinnear
Final11/14/200711/15/200711/15/2007APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/14/2007 at 12:51:35 PM. Contact: ###-####. ok final note signed card
Rough-In Permanent Service9/13/20079/13/20079/13/2007PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 9/13/2007 at 11:11:53 AM. Contact: ###-####. ok cover ri service approved by 370 9/13/07 am
Rough-In Permanent Service9/12/20079/13/20079/13/2007ACANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. see ri and p/s
Electrical Rough-In9/13/20079/13/20079/13/2007PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. called contr, left corr notice: nec 300.4 edge of bored holes shall be 1 1/4" from edge of framing members, 348.30(A) fmc shall be strapped within 12" of panels, 110.26(F)(1)(b) ducts over dedicated panel space shall have drip protection, 348.42 angle connectors shall not be used for concealed raceway installations, BCC inspection of raceways shall be made before cover
Permanent Service9/13/20079/13/20079/13/2007APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. p/s u/g n ok, 4 meters
Electrical Rough-In9/13/20079/13/20079/13/2007ACANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. cloned wrong permit
Electrical Rough-In8/3/20078/3/20078/3/2007PPASS
DetailsMike Kinnear
zane - 4 outlets underground Phone #: ###-#### ok cover under slab conduit & boxes
Application received  8/3/2007  