Temporary Service | 8/8/2007 | 8/8/2007 | 8/8/2007 | A | PASS |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook t/s u/g new ok
|
Final | 8/6/2007 | 8/6/2007 | 8/6/2007 | P | CANC |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook see t/s request
|
Temporary Service | 8/6/2007 | 8/7/2007 | 8/6/2007 | A | FAIL |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook corr. called 312.5 needs conn for GEC, 250.24 GEC shall be terminated to neutral at t/s, 110.12(C) clean dirt from t/s and meter, 110.3(A) tighten all locknuts and screws
|
Application received | | | 8/3/2007 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|