Final | 2/19/2008 | 2/20/2008 | 2/20/2008 | A | PASS |
Pat Lass
|
|
|
Final electrical inspection needed. Call ###-#### to gain access to home. Phone #: ###-#### Internet Inspection Request from: Alison Pennington final ok with survey for directory to be spacific and extensions on boxes by fire place and inuse cover and recep installed correctly by back door.
|
Rough-In Permanent Service | 8/29/2007 | 8/29/2007 | 8/29/2007 | P | PASS |
Pat Lass
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman R/I Ok P/S U/G N Ok
|
Conference | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | PART |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman talked about violations
|
Rough-In Permanent Service | 8/28/2007 | 8/28/2007 | 8/28/2007 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman corrections not made see last inspection
|
Reinspection Fee (no hold) | 8/28/2007 | 8/28/2007 | 8/28/2007 | P | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman corrections not made see last inspection
|
Rough-In Permanent Service | 8/9/2007 | 8/10/2007 | 8/10/2007 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman Underground covered without inspection. no electrode at house. gas pipe under house panel. box-fill. sheath not into box. 6 in free conductor. Id #6 neutral. staple romex within 8 in. grounds have no approved connection.
|
Application received | | | 8/9/2007 | | |
|
|
|
|
Issue permit | | | 8/9/2007 | | DONE |
|
|
|
|