Second Notice ELE | 11/15/2007 | 11/15/2007 | 12/4/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/2/2007 | 11/2/2007 | 11/15/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 11/1/2007 | 11/2/2007 | 11/2/2007 | A | PASS |
Jack Frank
|
|
|
3 pole breakers installed for furniture and 4/11 boxes on riser secured. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok no card
|
Final | 10/31/2007 | 10/31/2007 | 10/31/2007 | P | PART |
Mike Kinnear
|
|
|
Ready for a Final. Contact is Gary Nall. thanks Loren Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok temp occ no card available to sign corrections NEC605.7 & 314.23(A)
|
Conference | 10/15/2007 | 10/16/2007 | 10/16/2007 | A | PASS |
Mike Kinnear
|
|
|
need some eyes to look at the preaction riser passing over my ATS and MSB. GC/fitter doesnt understand the concept of floor to structural ceiling clear of any non electrical items above gear.need your help to convince.maybe some other options availble?call Loren Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok conf they need drip pan for sprinkler pipe over service
|
Permanent Service | 10/10/2007 | 10/11/2007 | 10/11/2007 | A | PASS |
William E Thomas
|
|
|
Joe - If possible please make this a later inspection. Phone #: ###-#### . 1. p/s u/g reconnect/new ok. . . 2. there is a ct-meter already in place at the transformer. .
|
Electrical Rough-In | 10/5/2007 | 10/5/2007 | 10/5/2007 | P | PASS |
William E Thomas
|
|
|
joe - ceiling Phone #: ###-#### . 1. drop ceiling ok to cover. .
|
Electrical Rough-In | 9/11/2007 | 9/11/2007 | 9/11/2007 | P | PASS |
Mike Kinnear
|
|
|
laran Phone #: ###-#### ok cover bathrm walls & hard lid ceilings note 8/24/07 oked walls except for bathrms & hard lid ceilings inspection written up wrong
|
Electrical Rough-In | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | FAIL |
Mike Kinnear
|
|
|
wayne Phone #: ###-####Note: for east evelator and main gear there has been no under ground inspection for the service conduits called left message for wayne
|
Electrical Rough-In | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | PASS |
Mike Kinnear
|
|
|
please check spacing on conduits underground. Bob looked at pipe runs this morning, just wanted to see some stakes installed to get some space on pipes. thanks Loren Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok cover under ground conduit
|
Electrical Rough-In | 8/13/2007 | 8/14/2007 | 8/14/2007 | A | PART |
Bob Reichert
|
|
|
call Loren for inspection of all outside and inside underground as well as east side office walls. please try to make inspection time around 10am if possible.thanks guys Phone #: ###-#### Internet Inspection Request from: Loren Ramsey walls east side and north wall east side only ok to cover. u/g will call for pm
|
Application received | | | 8/13/2007 | | |
|
|
|
|
Issue permit | | | 8/13/2007 | | DONE |
|
|
|
|