Final | 10/17/2007 | 10/17/2007 | 10/17/2007 | P | PASS |
William E Thomas
|
|
|
diane Phone #: ###-#### . 1. final ok. .
|
Electrical Rough-In | 8/22/2007 | 8/22/2007 | 8/22/2007 | P | PASS |
William E Thomas
|
|
|
colt Phone #: ###-#### 1. ri ok.
|
Electrical Rough-In | 8/21/2007 | 8/21/2007 | 8/21/2007 | P | FAIL |
Bob Reichert
|
|
|
cole Phone #: ###-#### met owner, left corr notice, nec 110.12(A) unused openings shall be closed, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm cable shall nott be stapled on edge and shall be secured within 12" of panel, BCC all make-up shall be done
|
Conference | 8/15/2007 | 8/15/2007 | 8/15/2007 | P | CANC |
William E Thomas
|
|
|
Colt ###-#### ///please call when on way to meet you there 1. talked with owner about circuits and locations of outlets.
|
Application received | | | 8/15/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/15/2007 | | DONE |
|
|
|
|