Final | 10/3/2007 | 10/3/2007 | 10/3/2007 | P | PASS |
Jack Frank
|
|
|
Final for kitchen and upstairs master bath. Please call prior to arrival to assure access. Thanks, Heath Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok
|
Electrical Rough-In | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | PASS |
Jack Frank
|
|
|
Call before arrival Phone #: ###-#### Internet Inspection Request from: Joe Thomas r/i ok corr made
|
Electrical Rough-In | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | FAIL |
Jack Frank
|
|
|
Please call prior to arrival. Ins. for Kitchen/nook remodel rough-in Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr fee due called 210.52(C)(1) shall maintain outlet spacingletf of kit sink, 210.52(A) outlet spacing wall din rm 210.52(B)(2) micro wave and under counter light not allowed on SABC250.140,134,138 needs 4 wire insulated neutral to oven, also no buried splices (phone cable)
|
Reinspection Fee (no hold) | 8/30/2007 | 8/30/2007 | 8/30/2007 | A | DONE |
Jack Frank
|
|
|
Please call prior to arrival. Ins. for Kitchen/nook remodel rough-in Phone #: ###-#### Internet Inspection Request from: Joe Thomas fee due corr.
|
Electrical Rough-In | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | PART |
Jack Frank
|
|
|
Please contact Jim @ ###-#### prior to arrival for access. Inspection for upstairs master bathroom Phone #: ###-#### Internet Inspection Request from: Joe okThomas
|
Application received | | | 8/15/2007 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|