Second Notice ELE | 3/3/2009 | 3/3/2009 | 7/29/2009 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by Deb Gooden
|
First Notice | 12/23/2008 | 12/23/2008 | 3/3/2009 | | DONE |
Mike Kinnear
|
|
|
|
Final | 12/22/2008 | 12/23/2008 | 12/23/2008 | A | PASS |
Mike Kinnear
|
|
|
CONTACT: CASEY WILDE Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok final note no esc permit in project
|
Conference | 11/17/2008 | 11/18/2008 | 11/18/2008 | A | DONE |
Mike Kinnear
|
|
|
phil ###-#### t/w tom hines IPCO sent one year demand for building as for nec220.87(1) four hundred amp service is ok. called phil from tri state & advised him of this. advised him that they had to fix code violations with the service. note no esc permit in project
|
Conference | 10/20/2008 | 10/22/2008 | 10/22/2008 | A | DONE |
Mike Kinnear
|
|
|
correction to renter nec 220.40 by 10/29/08 or further action could be taken i.e. power could be turned off
|
ELE-Aging Inspection | 10/15/2008 | 10/15/2008 | 10/20/2008 | | NR |
Mike Kinnear
|
|
|
t/w phil he will get load cals. for us
|
ELE-Aging Inspection | 8/15/2008 | 8/15/2008 | 8/22/2008 | | NR |
Mike Kinnear
|
|
|
t/w phil ###-#### he is going to email me the load cals. on the building
|
ELE-Aging Inspection | 6/13/2008 | 6/13/2008 | 6/17/2008 | | NR |
Mike Kinnear
|
|
|
t/w phil he needs to do load cal. on building & advise then we can meet renter
|
Conference | 8/20/2007 | 8/21/2007 | 8/21/2007 | A | PASS |
Mike Kinnear
|
|
|
Contact: Phil Bassick - 8:30 conference please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok conf service & grounding
|
Application received | | | 8/20/2007 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|
Conference | 11/3/2008 | 11/4/2008 | | P | |
Mike Kinnear
|
|
|
phil ###-####
|