Second Notice ELE | 9/26/2007 | 9/26/2007 | 10/12/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 9/4/2007 | 9/4/2007 | 9/26/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | PASS |
Jack Frank
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James ok card signed called needs to label panel
|
Electrical Rough-In | 8/31/2007 | 8/31/2007 | 8/31/2007 | P | FAIL |
Jack Frank
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt u/g ok still needs back-fed breaker device called
|
Electrical Rough-In | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | FAIL |
Jack Frank
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr 110.26(F)(1( clearence for panel, 300.4(A)(1)&(D) nail plates inside outside edges the same for cables parallel to framing members, 408.36(F) shall install back-fed device for main breaker 250.64(E) or 312.5 needs metal conn listed for grding or plastic conn. for GEC called
|
Reinspection Fee (no hold) | 8/31/2007 | 8/31/2007 | 8/31/2007 | A | DONE |
Jack Frank
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr fee due
|
Final | 8/27/2007 | 8/27/2007 | 8/27/2007 | P | CANC |
Jack Frank
|
|
|
tim Phone #: ###-#### needs bld or mis permit and shall request r/i not final
|
Application received | | | 8/27/2007 | | |
|
|
|
|
Issue permit | | | 8/27/2007 | | DONE |
|
|
|
|
Third Notice ELE | 10/12/2007 | 10/12/2007 | | | |
|
|
|
Second Notice has not been responded to.
|