Final | 10/23/2007 | 10/23/2007 | 10/23/2007 | P | PASS |
Pat Lass
|
|
|
jason Phone #: ###-#### final with survey for low voltage lights within 10 ft of pool.
|
Electrical Rough-In | 10/10/2007 | 10/11/2007 | 10/11/2007 | A | PART |
Pat Lass
|
|
|
jason - equal potential for swimming pool Phone #: ###-#### equal potential for swimming pool ok
|
Electrical Rough-In | 10/10/2007 | 10/10/2007 | 10/10/2007 | P | FAIL |
Bob Reichert
|
|
|
jason - equal potential for swimming pool Phone #: ###-#### called contr, left corr notice, nec 680.26(C) equipotential bonding grid shall extend 3' horizontally beyond inside walls of pool and extend under paved walking surface
|
Electrical Rough-In | 8/28/2007 | 8/28/2007 | 8/28/2007 | P | PART |
Jack Frank
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Hattie James; bonding inspection re-bar and pool light shell bond ok no u/g or E grid stub from light ok
|
Application received | | | 8/28/2007 | | |
|
|
|
|
Issue permit | | | 8/28/2007 | | DONE |
|
|
|
|