DOC - Permit Expired | 9/14/2009 | 9/14/2009 | 9/14/2009 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 12/9/2008 | 12/10/2008 | 12/10/2008 | A | PART |
Bob Reichert
|
|
|
Final inspection for shop only Phone #: ###-#### Internet Inspection Request from: Phil Baker shop part only ok to final, check panel schedule at full final
|
Electrical Rough-In | 10/8/2008 | 10/9/2008 | 10/9/2008 | A | PART |
Jack Frank
|
|
|
rough-in for shop wiring Phone #: ###-#### Internet Inspection Request from: Phil Baker ok
|
Final | 3/20/2008 | 3/21/2008 | 3/21/2008 | A | PART |
Pat Lass
|
|
|
On going remodel,request final for living areas(except kitchen) so home owner can move in furniture Phone #: ###-#### Internet Inspection Request from: Phil Baker outside, kitchen and utility room not ready for inspection. all closet lights shall be totally enclosed type. install receps for dinningroom counter. everything else is ok.
|
Electrical Rough-In | 9/26/2007 | 9/26/2007 | 9/26/2007 | P | PASS |
Jack Frank
|
|
|
phil Phone #: ###-#### r/i ok still needs outlet for counter in kit desk area 2ft 4 ft rule called contr will install outlet
|
Permanent Service | 9/25/2007 | 9/25/2007 | 9/25/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Phil Baker p/s u/g new ok
|
Electrical Rough-In | 9/25/2007 | 9/25/2007 | 9/25/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Phil Baker corr. called 210.52(B) all recepts in kit shall be on SABC, 210.52(C) address recepts left and right kit. sink, and desk counter in kit. 300.4 nail plates and 11/4" for cables parallel
|
Application received | | | 9/4/2007 | | DONE |
|
|
|
This permit was created on the web by Phil Baker
|