Final | 1/24/2008 | 1/24/2008 | 1/24/2008 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: chris green ok final
|
Case Summary (ELE) | | | 12/3/2007 | | DONE |
|
|
|
|
Rough-In Permanent Service | 9/17/2007 | 9/18/2007 | 9/18/2007 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: chris green ok cover ri p/s u/g n ok note corrections made note 210.52 wall spacing in kit if cabinet layout changes
|
Electrical Rough-In | 9/12/2007 | 9/13/2007 | 9/13/2007 | A | FAIL |
Jack Frank
|
|
|
Matt is the Journeyman for this job. Cabinet layout is in window and prints are under it, in the wall. Phone #: ###-#### Internet Inspection Request from: chris green corr. fee due , do not cover called, 300.4(A)(1) nail plates, 314.16 box fill, 314.43 screws not allowed in plastic boxes, 210.52(C) pantry shall be on small appliance brach circuit, note if island not flat acorr entire surface outlets not allowed below countertop size GEC to water for to table 250.66 needs #2 copper use plastic or listed metal conn for GEC terminat GEC within
|
Reinspection Fee (no hold) | 9/13/2007 | 9/13/2007 | 9/13/2007 | A | DONE |
Jack Frank
|
|
|
Matt is the Journeyman for this job. Cabinet layout is in window and prints are under it, in the wall. Phone #: ###-#### Internet Inspection Request from: chris green fee due corrections and not ready
|
Rough-In Permanent Service | 9/6/2007 | 9/6/2007 | 9/6/2007 | P | NR |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: chris green boise city code shall have am approved set of prints on job site & framing not complete in basement
|
Application received | | | 9/6/2007 | | DONE |
|
|
|
This permit was created on the web by chris green
|