Final | 12/20/2007 | 12/20/2007 | 12/20/2007 | P | PASS |
Bob Reichert
|
|
|
john - please call 1/2 hr prior to inspection Phone #: ###-#### corrections made, ok to final
|
Electrical Rough-In | 12/17/2007 | 12/17/2007 | 12/17/2007 | P | PASS |
Bob Reichert
|
|
|
john Phone #: ###-#### called owner, ok to pour concrete encased electrode, ok to cover u/g house to garage, left correction notice- nec 250.32(B)(1) grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode, 110.3(A) shall use strap suitable for installation at panel riser, 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member, BCC shall not install devices prior to inspection for free length of conductor
|
Conference | 10/10/2007 | 10/10/2007 | 10/10/2007 | P | DONE |
Bob Reichert
|
|
|
john Phone #: ###-#### Note: please call 1/2 hr prior to meet with talked about concrete encased electrode, service to shop, wiring building, inspection times
|
Application received | | | 9/7/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/7/2007 | | DONE |
|
|
|
|