Second Notice ELE | 9/26/2007 | 9/26/2007 | 9/27/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 9/10/2007 | 9/10/2007 | 9/26/2007 | | DONE |
Bob Reichert
|
|
|
|
Temporary Service | 9/10/2007 | 9/10/2007 | 9/10/2007 | A | PASS |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook corrections made, t/s u/g n ok
|
Temporary Service | 9/7/2007 | 9/7/2007 | 9/7/2007 | P | FAIL |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.14(A) connection of conductors to a terminal shall ensure a thoroughly good connection (gec at transformer), fee due
|
Application received | | | 9/7/2007 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|