Second Notice ELE | 9/26/2007 | 9/26/2007 | 10/1/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 9/12/2007 | 9/12/2007 | 9/26/2007 | | DONE |
Pat Lass
|
|
|
|
Electrical Rough-In | 9/11/2007 | 9/12/2007 | 9/12/2007 | A | PASS |
Pat Lass
|
|
|
call Steve with WGI for access into Plaza 2 building. Plaza 2 is building on far north side of WGI grounds. Drive all the way around facilty. Call Loren Ramsey at ###-#### if there are any problems. Thanks. Corrections have been made as requested by Bob R. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey
|
Final | 9/12/2007 | 9/12/2007 | 9/12/2007 | P | PASS |
Pat Lass
|
|
|
call Steve with WGI for access into Plaza 2 building. Plaza 2 is building on far north side of WGI grounds. Drive all the way around facilty. Call Loren Ramsey at ###-#### if there are any problems. Thanks. Corrections have been made as requested by Bob R. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey
|
Final | 9/11/2007 | 9/11/2007 | 9/11/2007 | P | CANC |
Bob Reichert
|
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, wrong type inspection, told contractor had to be ri 1st, see ri since it failed
|
Electrical Rough-In | 9/11/2007 | 9/11/2007 | 9/11/2007 | P | FAIL |
Bob Reichert
|
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr ,gave verbal corr notice,nec 300.11(A) no wiring shall be supported on grid or tiles, 725.3(B) abandoned low voltage wiring shall be removed, BCC shall provide seismic support wires, no tiles shall be installed, no violations shall be retained
|
Application received | | | 9/10/2007 | | |
|
|
|
|
Issue permit | | | 9/10/2007 | | DONE |
|
|
|
|