Permit Information
Permit NumberELE07-03308
StatusFinaled
Name MCLEAN ELECTRIC CO., INC.
Site Address 1070 N CURTIS RD Unit: 210
Project NameCURTIS PROF PLAZA
Customer Number 
ePlanReview 
Description
Add two outlets and one switch - initial certificate of value - $500
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE11/15/200711/15/200711/26/2007 DONE
First Notice has not been responded to.
First Notice10/22/200710/22/200711/15/2007 DONE
DetailsMike Kinnear
Final10/22/200710/22/200710/22/2007PPASS
DetailsMike Kinnear
spencer Phone #: ###-#### ok final note signed card
Final10/18/200710/18/200710/18/2007PCANC
DetailsBob Reichert
spencer Phone #: ###-#### wrong type request, see ri
Electrical Rough-In10/18/200710/18/200710/18/2007PPASS
DetailsBob Reichert
spencer Phone #: ###-#### called contr, left message, corrections made, ok to cover ceiling only
Final10/17/200710/17/200710/17/2007PNR
DetailsBob Reichert
spencer Phone #: ###-#### looked at job, electricians still working, corrections not made, told journeyman to have called in when done
Final10/15/200710/15/200710/15/2007PFAIL
DetailsBob Reichert
spencer - re-inspection Phone #: ###-#### called contractor, left correction notice, fee due, nec 725.3 the accessible portion of cl2,3, and pltc cable shall be removed if not terminated, 725.58 low voltage cables shall not be attached to raceways for support, 314.25 boxes shall have covers installed, 300.11 raceways shall be securely fastened in place, independent support wires shall be fastened at each end, BCC fixtures shall utilize seismic wires, corrections not made,this is partial list until can see ceiling
Reinspection Fee (no hold)10/15/200710/15/200710/15/2007PFAIL
DetailsBob Reichert
spencer - re-inspection Phone #: ###-#### see failed inspection
Final10/12/200710/12/200710/12/2007PFAIL
DetailsBob Reichert
spencer Phone #: ###-#### met contractor, left correction notice to owner and contr, BCC no violations shall be retained, ceiling grid shall not support cables or raceways, all tiles shall be removed for ceiling inspection
Electrical Rough-In9/24/20079/24/20079/24/2007PPASS
DetailsBob Reichert
Spencer, ###-#### walls only ok to cover
Application received  9/24/2007  
Issue permit  9/24/2007 DONE