Temporary Service | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | PASS |
Jack Frank
|
|
|
Olga Phone #: ###-#### t/s o/h new ok
|
Temporary Service | 10/29/2007 | 10/29/2007 | 10/29/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/29/2007 at 7:19:12 AM. Contact: ###-####. corr. clean dirt from t/s 250 24 tie GEC and neutral together called
|
Reinspection Fee (no hold) | 10/29/2007 | 10/29/2007 | 10/29/2007 | P | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/29/2007 at 7:19:12 AM. Contact: ###-####. fee due not all violations corrected
|
Temporary Service | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | FAIL |
Jack Frank
|
|
|
Olga Phone #: ###-#### called left message fee due, 400.8(1) cord used as fixed wiring, 408.41 neutrals doubled up under terminals, 110.12(C) clean dirt from t/s 230.24(B)(1) needs 10ft from drip loop to grade level, 312.5 conn for GEC, 110.3(A) tighten screws and fittings, 310.16 #12 protected by 30 amp wire at 2 pole breaker
|
Reinspection Fee (no hold) | 10/4/2007 | 10/4/2007 | 10/4/2007 | A | DONE |
Jack Frank
|
|
|
Olga Phone #: ###-#### fee due corr.
|
Application received | | | 10/3/2007 | | |
|
|
|
|
Issue permit | | | 10/3/2007 | | DONE |
|
|
|
|