Final | 6/16/2008 | 6/16/2008 | 6/16/2008 | P | PASS |
Pat Lass
|
|
|
Jay Phone #: ###-#### - please call 1/2 hr prior to inspection no esc permit final ok
|
Final | 6/12/2008 | 6/13/2008 | 6/13/2008 | A | FAIL |
Pat Lass
|
|
|
Jay Phone #: ###-#### required recep above counter GFCI protect kitchen, garage, laundry sink. and jetted tub arc fault protect master bedroom lights. location and type of closet lightes. recep position and boxes flush
|
Electrical Rough-In | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Pat Lass
|
|
|
jay or travis at ###-#### Phone #: ###-####
|
Electrical Rough-In | 2/26/2008 | 2/27/2008 | 2/27/2008 | A | FAIL |
Bob Reichert
|
|
|
Jay Phone #: ###-#### or Travis at ###-#### called, left correction notice, NEC 334.30 nm cable shall be stapled within 12" of boxes, cabinets and every 4 1/2', 314.17(C) nm cable sheath shall extend minimum 1/4" inside box, and be secured within 8" of single gang boxes, 300.4(A)(1) edge of bored holes shall be 1 1/4" from face of framing members or protected by steel plate, 210.52(E) at least one receptacle shall be installed at front of dwelling and be accessible at grade level, BCC all make-up shall be done and boxes installed, tub is listed
|
Electrical Rough-In | 2/20/2008 | 2/20/2008 | 2/20/2008 | P | CANC |
Bob Reichert
|
|
|
As late as possible and please call prior to inspection-travis Phone #: ###-#### see conference
|
Conference | 2/20/2008 | 2/20/2008 | 2/20/2008 | P | DONE |
Bob Reichert
|
|
|
As late as possible and please call prior to inspection-travis Phone #: ###-#### met owner, talked about free length of conductor, several grounds cut too short,, 2' wall space, 1 1/4 for holes and nm cable, make-up, boxes to be installed, is builder doing the wirng?
|
Permanent Service | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Pat Lass
|
|
|
Travis; Phone #: ###-#### - please call 1/2 hr prior to inspection - Internet Inspection Request from: Cathy Weisshaupt P/S U/g N Ok
|
Permanent Service | 1/10/2008 | 1/11/2008 | 1/11/2008 | A | NR |
Pat Lass
|
|
|
travis Note:please call 1/2 hr prior to inspection Phone #: ###-####
|
Conference | 12/13/2007 | 12/14/2007 | 12/14/2007 | P | PART |
Pat Lass
|
|
|
Jay Please call 1/2 hour before going out Phone #: ###-#### talked about general requirements and service and sub panel
|
Application received | | | 10/4/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/4/2007 | | DONE |
|
|
|
|