Third Notice ELE | 3/20/2008 | 3/20/2008 | 3/25/2008 | | DONE |
Tisha Gallop
|
|
|
This permit finaled on the web by Celinda Winters
|
Second Notice ELE | 3/3/2008 | 3/3/2008 | 3/20/2008 | | DONE |
Tisha Gallop
|
|
|
First Notice has not been responded to.
|
First Notice | 2/19/2008 | 2/19/2008 | 3/3/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 2/15/2008 | 2/19/2008 | 2/19/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to final, signed occupancy card
|
Electrical Rough-In | 1/18/2008 | 1/22/2008 | 1/22/2008 | A | PASS |
Bob Reichert
|
|
|
Wall Rough-in office area Phone #: ###-#### Internet Inspection Request from: Celinda Winters walls only ok to cover
|
Permanent Service | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contractor, told passed yesterday, talked about grounding at service
|
Rough-In Permanent Service | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters wrong type request, see p/s
|
Permanent Service | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s o/h n ok
|
Rough-In Permanent Service | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters service not close to being ready, left correction notice, nec 110.3(B) and BCC 4-05-33(A)(B) all equipment shall be listed and labelled by a nationally recognized testing lab,BCC approved set of plans shall be on job, only device make-up ok in greenhouse area, plans shall classify nema rating for equipment
|
Application received | | | 10/5/2007 | | |
|
|
|
|
Issue permit | | | 10/5/2007 | | |
|
|
|
|