Electrical Rough-In | 10/15/2007 | 10/16/2007 | 10/16/2007 | A | PASS |
Jack Frank
|
|
|
BILL ###-#### ok
|
Electrical Rough-In | 10/15/2007 | 10/15/2007 | 10/15/2007 | P | FAIL |
Jack Frank
|
|
|
bill Phone #: ###-#### corr called all corr. not made still loose crimps, box fill ,6" free length,
|
Electrical Rough-In | 10/11/2007 | 10/12/2007 | 10/12/2007 | A | FAIL |
Bob Reichert
|
|
|
bill Phone #: ###-#### called owner, left correction notice, nec 314.20 boxes shall be flush with finished surface- outside garage doors lights, 300.4(D) edge of nm cable shall be 1 1/4" form edge of framing member, 300.14 at least 6" of free conductor shall be provided in boxes, 110.12(C) there shall be no broken boxes(openings shall be closed), 110.14(A) connection of conductors shall ensure a thoroughly good connection (ground crimps) Note: no service or panel, see ele07-03473
|
Application received | | | 10/11/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/11/2007 | | |
|
|
|
|