Final | 12/17/2007 | 12/17/2007 | 12/17/2007 | A | PASS |
Bob Reichert
|
|
|
see ele07-04130 to final, called contractor for his ok to final this permit, since other contractor got called in on job to finish
|
Electrical Rough-In | 10/21/2007 | 10/22/2007 | 10/22/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/21/2007 at 9:43:58 PM. Contact: ###-####. corrections made, ric ok
|
Electrical Rough-In | 10/18/2007 | 10/19/2007 | 10/19/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/18/2007 at 8:36:06 PM. Contact: ###-####. corr called nail plates and 11/4", 210.11(C)(2) 20 amp laundry circuit shall only feeds recepts in laundry rm, 250.24 isolate grds and netrals basement sub panel (bond screw), 334.30 shall not staple romex on edge
|
Application received | | | 10/15/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/15/2007 | | DONE |
|
|
|
|