Second Notice ELE | 11/15/2007 | 11/15/2007 | 11/16/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/1/2007 | 11/1/2007 | 11/15/2007 | | DONE |
Jack Frank
|
|
|
|
Permanent Service | 10/31/2007 | 11/1/2007 | 11/1/2007 | A | PASS |
Jack Frank
|
|
|
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Tyler Bowen r/i ok p/s u/g new ok
|
Final | 11/1/2007 | 11/1/2007 | 11/1/2007 | A | PASS |
Jack Frank
|
|
|
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Tyler Bowen
|
Permanent Service | 10/29/2007 | 10/30/2007 | 10/30/2007 | A | FAIL |
Jack Frank
|
|
|
underground and permanent service inpsection. Meter pedistal for sign Phone #: ###-#### Internet Inspection Request from: Tyler Bowen corr called needs conn for GEC, BCC u/g covered before inspection, 300.10&12 MC in sign pole enclosure shall terminate in bos or conduit body, 250.56 needs 2 grd rods for p/s, 342.46 IMC needs bushings
|
Reinspection Fee (no hold) | 10/30/2007 | 10/30/2007 | 10/30/2007 | A | DONE |
Jack Frank
|
|
|
underground and permanent service inpsection. Meter pedistal for sign Phone #: ###-#### Internet Inspection Request from: Tyler Bowen corr. fee due
|
Permanent Service | 10/25/2007 | 10/26/2007 | 10/26/2007 | A | CANC |
Jack Frank
|
|
|
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Tyler Bowen
|
Application received | | | 10/25/2007 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|