Temporary Service | 2/26/2009 | 2/26/2009 | 2/26/2009 | A | PASS |
Jack Frank
|
|
|
|
Temporary Service | 8/25/2008 | 8/25/2008 | 8/25/2008 | A | PART |
Jack Frank
|
|
|
|
Temporary Service | 11/15/2007 | 11/15/2007 | 11/15/2007 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/15/2007 at 6:46:38 AM. Contact: ###-####. still needs to wire job trailer no final, t/s u/g new ok
|
Temporary Service | 11/6/2007 | 11/6/2007 | 11/6/2007 | P | FAIL |
Jack Frank
|
|
|
temp pole inspection Internet Inspection Request from: Rowdy Monroe corr. called use listed or plastic conn for GEC, 110.3(B) use manufactures listed breakers only, 110.12(A) seal unused openings, T400.5(A) provide correct overcurrent protection for #8 cord, 590.6(B)(1) gfci for 249V cord cap recepts
|
Application received | | | 11/6/2007 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|