Second Notice ELE | 3/20/2008 | 3/20/2008 | 3/24/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 2/25/2008 | 2/25/2008 | 3/20/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 2/25/2008 | 2/25/2008 | 2/25/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman corrections made, signed occupancy card, ok to final
|
Final | 2/21/2008 | 2/21/2008 | 2/21/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman called, left correction notice, NEC 314.23(C) boxes shall be securely mounted in a finished surface, 406.4 receptacles shall be securely fastened in place, 352.30(A) rnc at service shall be securely fastened within 3' of box,408.4 shall provide circuit directory for house panel, 422.31(B) shall provide disconnect for heater in #201, BCC all work shall be completed for final, i.e. air condioners shall be wired
|
Final | 2/21/2008 | 2/21/2008 | 2/21/2008 | A | NH |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman called contractor, locked up, told to call for pm, fee due
|
Permanent Service | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/6/2007 at 10:18:32 AM. Contact: ###-####. correction made, p/s, u/g, n, ok (5 meters)
|
Rough-In Permanent Service | 11/19/2007 | 11/20/2007 | 11/20/2007 | A | PART |
Mike Kinnear
|
|
|
Stairs have been installed and the pipe that is under the service will be moved. This is not the telephone or the t.v conduit. Any questions pleas call Craig at 941 9750 Thank you Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ok cover ri note service groundinding & sub panels ok but they have not removed foreign conduit under main panel so it fails until they move it called contractor
|
Rough-In Permanent Service | 11/12/2007 | 11/13/2007 | 11/13/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman called needs stairs installed , and remove phone conduit below p/s
|
Final | 11/12/2007 | 11/13/2007 | 11/12/2007 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman Inspection cancelled from web by: Shaun Kirkman
|
Application received | | | 11/12/2007 | | DONE |
|
|
|
This permit was created on the web by Shaun Kirkman
|