Second Notice ELE | 6/10/2008 | 6/10/2008 | 6/11/2008 | | DONE |
Patricia Smith
|
|
|
This permit finaled on the web by Todd Holbrook
|
First Notice | 5/21/2008 | 5/21/2008 | 6/10/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 5/21/2008 | 5/21/2008 | 5/21/2008 | P | PASS |
Bob Reichert
|
|
|
chris Phone #: ###-#### corrections made, signed occupancy card, ok to final
|
Final | 5/20/2008 | 5/20/2008 | 5/20/2008 | P | FAIL |
Bob Reichert
|
|
|
chris Phone #: ###-#### called contractor,left message, left correction notice, NEC 210.8(B) baths shall have gfci receptacles, 422.31(B) dishwasher shall be provided with disconnect, lockable,BCC shall follow approved plans for energy conservation-dual level switching for lighting, shall uncover floor box for u/g inspection or demo out, shall call for core and shell final before tenant final
|
Rough-In Permanent Service | 11/12/2007 | 11/13/2007 | 11/13/2007 | A | PASS |
Bob Reichert
|
|
|
Chris ###-#### Internet Inspection Request from: Todd Holbrook ric walls and ceiling only, met contr, no u/g seen will have to cut up concrete to see to floor box see 7-3392 for core, neither permit had u/g inspected, p/s u/g n pk
|
Application received | | | 11/12/2007 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|