complete electric $67,486 per initial cert of value ///final value is $40,000 per faxed document 6-12-08ps
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE6/10/20086/10/20086/12/2008 DONE
DetailsPatricia Smith
First Notice has not been responded to.
First Notice5/23/20085/23/20086/10/2008 DONE
DetailsJack Frank
Final5/22/20085/23/20085/23/2008APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 5/22/2008 at 10:25:42 AM. Contact: ###-####. survey gfci for disposal recepts, 314.3 bond bushinf for emt in plastic sprinkler control box called final ok card signed
Electrical Rough-In3/26/20083/26/20083/26/2008PPART
DetailsJack Frank
told ele contr that general needs to remove phone or caty conduit from below p/s panel
Permanent Service3/26/20083/26/20083/26/2008PPASS
DetailsJack Frank
pam Phone #: ###-#### contr will bond can and water systems p/s u/g new ok
Electrical Rough-In3/26/20083/26/20083/26/2008PPART
DetailsJack Frank
###-#### - pam Note: underground pipe for lighting u/g for 1pole light and sign lighting okwest side
Rough-In Permanent Service1/28/20081/28/20081/28/2008PCANC
DetailsJack Frank
darlene Phone #: ###-#### see r/i request, p/s not ready
Electrical Rough-In1/28/20081/28/20081/28/2008PPASS
DetailsJack Frank
darlene Phone #: ###-#### r/i ok all walls and hard ceilings
Electrical Rough-In1/24/20081/25/20081/25/2008AFAIL
DetailsJack Frank
andy Phone #: ###-#### corr. called outlet spacing, nail plates, no screws in plastic boxes secure cables within 12" of panels, use plastic conn. for GEC
Reinspection Fee (no hold)1/25/20081/25/20081/25/2008ADONE
DetailsJack Frank
andy Phone #: ###-#### corr. fee due
Electrical Rough-In1/16/20081/17/20081/17/2008PCANC
DetailsJack Frank
darlene Note cover Phone #: ###-####
see added conf
Conference1/17/20081/17/20081/17/2008PDONE
DetailsJack Frank
darlene Note cover Phone #: ###-####
conference ok only needs to correct p/s grounding, bath rm circuit, 11/4", protect at attic accesses, 6" free length, outlet spacing, secure MC 12" of boxes
Application received  11/15/2007  