Telephone call | | | 6/4/2008 | | DONE |
|
|
|
I called again at 1:30 and she is in boise and will return my call tomarrow for final value
|
Telephone call | | | 6/4/2008 | | DONE |
|
|
|
I talk to owner and he will fax me the contract with bid for value 1:45 pm
|
Telephone call | | | 5/27/2008 | | DONE |
|
|
|
lft ms with receptionist regarding the final value differences from 120,000 to 147,616 - she will call be back 10:45 am
|
Second Notice ELE | 4/23/2008 | 4/23/2008 | 5/5/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 4/2/2008 | 4/2/2008 | 4/23/2008 | | DONE |
William E Thomas
|
|
|
|
Final | 4/2/2008 | 4/2/2008 | 4/2/2008 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen . .1. final ok. . .
|
Final | 4/1/2008 | 4/1/2008 | 4/1/2008 | P | PART |
Bob Reichert
|
|
|
Asking for a final on Kitchen Line only. Phone #: ###-#### Internet Inspection Request from: Paula Gietzen kitchen areas only ok, need to see rest of job
|
Electrical Rough-In | 3/17/2008 | 3/18/2008 | 3/18/2008 | A | PASS |
Bob Reichert
|
|
|
above ceiling inspection Phone #: ###-#### Internet Inspection Request from: Paula Gietzen ok to cover ceiling
|
Conference | 3/10/2008 | 3/11/2008 | 3/11/2008 | A | CANC |
Jack Frank
|
|
|
Underground site work Phone #: ###-#### Internet Inspection Request from: Paula Gietzen
|
Electrical Rough-In | 3/11/2008 | 3/11/2008 | 3/11/2008 | A | PART |
Jack Frank
|
|
|
Underground site work Phone #: ###-#### Internet Inspection Request from: Paula Gietzen u/g ok
|
Electrical Rough-In | 3/7/2008 | 3/10/2008 | 3/10/2008 | A | FAIL |
Bob Reichert
|
|
|
Underground inspection. Trenching and pipe for sign and pole bases Phone #: ###-#### Internet Inspection Request from: Paula Gietzen called contractor, left correction notice and card, BCC shall not cover u/g before inspection, shall provide proper bedding per NEC 300.5, no rocks in u/g. see 1st pole base on right middle of lot for do not cover card
|
Electrical Rough-In | 2/19/2008 | 2/19/2008 | 2/19/2008 | P | PASS |
Bob Reichert
|
|
|
Wall - Rough in Doug Gietzen is on site ###-#### Phone #: ###-#### Internet Inspection Request from: Paula Gietzen walls only ok to cover
|
Permanent Service | 2/19/2008 | 2/19/2008 | 2/19/2008 | P | PASS |
Bob Reichert
|
|
|
Wall - Rough in Doug Gietzen is on site ###-#### Phone #: ###-#### Internet Inspection Request from: Paula Gietzen p/s u/g n ok
|
Rough-In Permanent Service | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PART |
Mike Kinnear
|
|
|
Request underground inspection Phone #: ###-#### Internet Inspection Request from: Paula Gietzen ok cover under slab conduit note service not ready
|
Electrical Rough-In | 12/19/2007 | 12/19/2007 | 12/19/2007 | P | PASS |
William E Thomas
|
|
|
. 1. concrete encased electrode ok for cover in footing. .
|
Electrical Rough-In | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | FAIL |
William E Thomas
|
|
|
U-Fer Ground Inspection only. Concrete guys want to pour after 1pm Friday, December 07,2007. Thank you. Phone #: ###-#### Internet Inspection Request from: Paula Gietzen . 1. Electrode not in proper position, needs to be on the bottom of the footing. .
|
Temporary Service | 11/21/2007 | 11/21/2007 | 11/21/2007 | P | PART |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen needs inspection for job shack feeder t/s o/h new ok
|
Temporary Service | 11/20/2007 | 11/21/2007 | 11/21/2007 | A | CANC |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen t/w contractor temp not ready he will recall back in with ready
|
Application received | | | 11/16/2007 | | |
|
|
|
|
Issue permit | | | 11/16/2007 | | DONE |
|
|
|
|