Third Notice | | 4/23/2010 | 4/23/2010 | | DONE |
Rita DeYoung
|
|
|
worked with Jamie final fees due on ele08-00409
|
Case Summary (ELE) | | | 3/17/2010 | | DONE |
|
|
|
|
First Notice | 4/27/2009 | 4/27/2009 | 12/28/2009 | | DONE |
Jack Frank
|
|
|
|
Final | 4/27/2009 | 4/27/2009 | 4/27/2009 | P | PASS |
Jack Frank
|
|
|
joe Phone #: ###-#### ok card signed, also anop
|
Electrical Rough-In | 4/17/2009 | 4/20/2009 | 4/20/2009 | A | PART |
Bob Reichert
|
|
|
Joe Phone #: ###-#### ceilings alf ok to cover anop, could not add esc response
|
Electrical Rough-In | 2/24/2009 | 2/25/2009 | 2/25/2009 | A | PASS |
Bob Reichert
|
|
|
Joe Phone #: ###-#### walls only anop ok to cover, assisted lining
|
ELE-Aging Inspection | 2/13/2009 | 2/13/2009 | 2/13/2009 | | DONE |
Bob Reichert
|
|
|
project suc, not ready for full final
|
Final | 12/11/2008 | 12/12/2008 | 12/12/2008 | A | PART |
Bob Reichert
|
|
|
Joe Phone #: ###-#### signed t/o cards for alf dining, halls and aid station only
|
Final | 12/11/2008 | 12/11/2008 | 12/11/2008 | P | PART |
Bob Reichert
|
|
|
joe - partial Phone #: ###-#### ok to final alf dining room, halls, and aid station
|
Electrical Rough-In | 11/19/2008 | 11/20/2008 | 11/20/2008 | A | PASS |
Bob Reichert
|
|
|
Joe Phone #: ###-#### assisted living facility (alf) halls (3) ceilings and dining room ceiling ok to cover- will see rest of halls at remodel
|
Electrical Rough-In | 10/17/2008 | 10/20/2008 | 10/20/2008 | A | PASS |
Bob Reichert
|
|
|
joe Phone #: ###-#### dining room soffits assisted living ok to cover, could not add esc inspection
|
Electrical Rough-In | 9/30/2008 | 9/30/2008 | 9/30/2008 | P | PASS |
Bob Reichert
|
|
|
joe Phone #: ###-#### ok to cover walls only alf dining and ceiling in passage to aid station, could not add esc comment
|
Electrical Rough-In | 6/23/2008 | 6/24/2008 | 6/24/2008 | A | PART |
Bob Reichert
|
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt aid station walls only anop ok to cover
|
Final | 6/13/2008 | 6/16/2008 | 6/16/2008 | A | PART |
Bob Reichert
|
|
|
joe - ###-####- on east and west additions - not being modified, corrections made, ok to final, signed temporary occupancy card copy, check outside receptacles
|
Override - Parcel Holds | | | 6/13/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/13/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/13/2008 | | |
|
|
|
|
Conference | 6/10/2008 | 6/12/2008 | 6/12/2008 | A | DONE |
William E Thomas
|
|
|
SEE TOM . .1. done. . .
|
Final | 6/9/2008 | 6/10/2008 | 6/10/2008 | A | FAIL |
Bob Reichert
|
|
|
joe - ###-#### - on the 2 new additions not being modified met electrician, left correction notice, NEC 250.122 equipment grounds shall be per table, 408.4 citcuit directory shall be clear, concise, and explanatory for each circuit, 422.31(B) shall provide disconnect for water heaters, 250.104(A)(1) shall bond hot and cold water piping per table 250.122, BCC shall install all switch plates and fixtures
|
Override - Parcel Holds | | | 6/10/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/10/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/10/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/9/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/9/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 6/9/2008 | | |
|
|
|
|
Electrical Rough-In | 5/12/2008 | 5/13/2008 | 5/13/2008 | A | PASS |
Jack Frank
|
|
|
joe - ###-#### Note: ceiling inspection on the 2 editions in assist living ok to cover ceilings in both additions (halls only)
|
Permanent Service | 5/13/2008 | 5/13/2008 | 5/13/2008 | A | PASS |
Bob Reichert
|
|
|
joe - ###-#### Note: ceiling inspection on the 2 editions in assist living p/s u/g n ok
|
Override - Parcel Holds | | | 5/12/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 5/12/2008 | | |
|
|
|
|
Electrical Rough-In | 4/25/2008 | 4/28/2008 | 4/28/2008 | P | PART |
Jack Frank
|
|
|
JOE NOTE PARTIAL R/I Phone #: ###-#### had conference with contr about p/s
|
Override - Parcel Holds | 4/25/2008 | 1/1/1900 | 4/25/2008 | | |
|
|
|
R/I
|
Conference | 4/7/2008 | 4/8/2008 | 4/8/2008 | A | DONE |
Bob Reichert
|
|
|
joe Phone #: ###-#### looked at possibilities for new service for existing building and new addition - locations, layouts, room remodel, phone board remodel. Reviewed fire alarm circuits ahead of main at other facility.
|
Override - Parcel Holds | 4/7/2008 | 1/1/1900 | 4/7/2008 | | |
|
|
|
conference only
|
Electrical Rough-In | 3/18/2008 | 3/18/2008 | 3/18/2008 | P | PASS |
Bob Reichert
|
|
|
joe Note: underground Phone #: ###-#### u/g front side ok to cover from transformer headed sw to sidewalk
|
Override - Parcel Holds | 3/18/2008 | 1/1/1900 | 3/18/2008 | | |
|
|
|
not ele08-00409
|
Electrical Rough-In | 2/5/2008 | 2/5/2008 | 2/5/2008 | P | PASS |
Bob Reichert
|
|
|
JOE nOTE: PARTIAL R/I Phone #: ###-#### ric walls and hard lids west wing anop ok
|
Electrical Rough-In | 1/24/2008 | 1/24/2008 | 1/24/2008 | P | PASS |
Bob Reichert
|
|
|
joe Phone #: ###-#### ric ok walls and hard lids only east wing anop
|
Electrical Rough-In | 12/3/2007 | 12/3/2007 | 12/3/2007 | P | PASS |
Bob Reichert
|
|
|
joe Phone #: ###-#### u/g next to adjacent building for 3 stub-ups ok to pour, concrete encased electrode ok to pour
|
Application received | | | 11/30/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/30/2007 | | DONE |
|
|
|
|