Electrical Rough-In | 5/20/2008 | 5/21/2008 | 5/21/2008 | A | PASS |
Jack Frank
|
|
|
Sam, please come before 10:00 if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt r/i for smoke detectors ok final ok
|
Final | 5/21/2008 | 5/21/2008 | 5/21/2008 | A | PASS |
Jack Frank
|
|
|
Sam, please come before 10:00 if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt final ok by 370
|
Change Status to I | | | 5/16/2008 | | DONE |
|
|
|
bob reichert called in to reopen this permit
|
Final | 5/14/2008 | 5/15/2008 | 5/15/2008 | A | PASS |
Bob Reichert
|
|
|
sam Phone #: ###-#### ok to final
|
Final | 5/12/2008 | 5/14/2008 | 5/14/2008 | A | NR |
Bob Reichert
|
|
|
sam Phone #: ###-#### met homeowner, told he had to safe-off fan wiring at box, install all plates for switches and receptacles, label panel, install in-use cover for outside receptacle, rest ok
|
Electrical Rough-In | 12/10/2007 | 12/10/2007 | 12/10/2007 | P | PASS |
Bob Reichert
|
|
|
sam Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 12/5/2007 | 12/6/2007 | 12/6/2007 | P | FAIL |
Bob Reichert
|
|
|
sam Phone #: ###-#### met owner, left correction notice, 334.10(A) nm cables shall be permitted for exposed and concealed work in normally dry locations, 410.8 closet light shall be installed to meet clearances over combustible material, BCC all make-up shall be done
|
Application received | | | 12/5/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/5/2007 | | DONE |
|
|
|
|