Permit Information
Permit NumberELE07-04034
StatusFinaled
Name ACE ELECTRIC AND CONTROL
Site Address 1119 N 21ST ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Gut and Rewire of existing home, new basement and rear addition
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/10/20084/11/20084/11/2008APASS
DetailsWilliam E Thomas
House is open around 8 am Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
. .1. final ok. . .
Permanent Service12/18/200712/18/200712/18/2007APASS
DetailsPat Lass
final ufer inspection needed for service Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
P/S U/G R Ok
Rough-In Permanent Service12/13/200712/13/200712/13/2007PPART
DetailsPat Lass
need ufer inspection, installed per directions from Jim the electrical supervisor. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
Approved by Jim for this job.
ok for concrete.
Rough-In Permanent Service12/11/200712/12/200712/12/2007AFAIL
DetailsMike Kinnear
ufer inspection needed, attached ground wire to foundation to encase in concrete. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson grounding electroded is not at footing & foundation. advised them they could go to rebar & expose it & with the proper fitted & we see it that would work. called monty & left message
Electrical Rough-In12/6/200712/7/200712/7/2007PPASS
DetailsBob Reichert
Rough inspection and ufer inspection Phone #: ###-#### Internet Inspection Request from: Monty Adkinson correction for ri only made, concrete encased electrode shall have clean-up for stem wall to remove mud and black substance removed from concrete. They will re-call for electrode.
Electrical Rough-In12/6/200712/6/200712/6/2007AFAIL
DetailsPat Lass
Need rough inspection and permanent service inspection. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson
no concrete encassed electrode
Protect romex and 6 in free conductor.
Application received  12/6/2007 DONE
This permit was created on the web by Monty Adkinson