Final | 4/10/2008 | 4/11/2008 | 4/11/2008 | A | PASS |
William E Thomas
|
|
|
House is open around 8 am Phone #: ###-#### Internet Inspection Request from: Monty Adkinson . .1. final ok. . .
|
Permanent Service | 12/18/2007 | 12/18/2007 | 12/18/2007 | A | PASS |
Pat Lass
|
|
|
final ufer inspection needed for service Phone #: ###-#### Internet Inspection Request from: Monty Adkinson P/S U/G R Ok
|
Rough-In Permanent Service | 12/13/2007 | 12/13/2007 | 12/13/2007 | P | PART |
Pat Lass
|
|
|
need ufer inspection, installed per directions from Jim the electrical supervisor. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson Approved by Jim for this job. ok for concrete.
|
Rough-In Permanent Service | 12/11/2007 | 12/12/2007 | 12/12/2007 | A | FAIL |
Mike Kinnear
|
|
|
ufer inspection needed, attached ground wire to foundation to encase in concrete. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson grounding electroded is not at footing & foundation. advised them they could go to rebar & expose it & with the proper fitted & we see it that would work. called monty & left message
|
Electrical Rough-In | 12/6/2007 | 12/7/2007 | 12/7/2007 | P | PASS |
Bob Reichert
|
|
|
Rough inspection and ufer inspection Phone #: ###-#### Internet Inspection Request from: Monty Adkinson correction for ri only made, concrete encased electrode shall have clean-up for stem wall to remove mud and black substance removed from concrete. They will re-call for electrode.
|
Electrical Rough-In | 12/6/2007 | 12/6/2007 | 12/6/2007 | A | FAIL |
Pat Lass
|
|
|
Need rough inspection and permanent service inspection. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson no concrete encassed electrode Protect romex and 6 in free conductor.
|
Application received | | | 12/6/2007 | | DONE |
|
|
|
This permit was created on the web by Monty Adkinson
|