Final | 12/26/2007 | 12/27/2007 | 12/27/2007 | A | PASS |
Mike Kinnear
|
|
|
brian - reinspection Phone #: ###-#### ok final corrections made
|
Final | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | FAIL |
Jack Frank
|
|
|
brian Phone #: ###-#### corr called 225.30 and 36 only one branch circuit allowed to detached shop, and needs disconnect at shop
|
Electrical Rough-In | 12/12/2007 | 12/13/2007 | 12/13/2007 | A | PASS |
Bob Reichert
|
|
|
brian Note: if any question call him Phone #: ###-#### called contractor, left survey, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, ric rear structure ok to cover, Note: this structure must be attached to adjacent structure for branch circuits as installed to be ok
|
Application received | | | 12/12/2007 | | |
|
|
|
|
Issue permit | | | 12/12/2007 | | DONE |
|
|
|
|