Final | 3/28/2008 | 3/31/2008 | 3/31/2008 | A | PASS |
Bob Reichert
|
|
|
READY FOR INSPECTION Phone #: ###-#### Internet Inspection Request from: gary batten called contractor, left survey 110.3(B) equipment shall be installed per manufacturers instructions (afci), ok to final
|
Electrical Rough-In | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Mike Kinnear
|
|
|
electrician is nick felsted Phone #: ###-#### Internet Inspection Request from: gary batten ok cover ri
|
Final | 12/20/2007 | 12/21/2007 | 12/20/2007 | A | CANC |
Bob Reichert
|
|
|
electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer Inspection cancelled from web by: gary batten
|
Rough-In Permanent Service | 12/17/2007 | 12/18/2007 | 12/18/2007 | A | FAIL |
Bob Reichert
|
|
|
Electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left correction notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) receptacles shall be spaced such that no point along floor line is more than 6' from an outlet,334.30 nm cable shall not be stapled on edge, 314.20 in walls of combustible material, boxes shall be flush with the finished surface
|
Application received | | | 12/17/2007 | | DONE |
|
|
|
This permit was created on the web by Jarrod Clymer
|