Final | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | PASS |
Mike Kinnear
|
|
|
SCOTT Phone #: ###-#### corections made ok final
|
Final | 12/26/2007 | 12/27/2007 | 12/27/2007 | A | FAIL |
Bob Reichert
|
|
|
scott Phone #: ###-#### called contr, left correction notice, nec 408.4 circuit directory shall be clear, concise and explanatory for each circuit, 110.12(A) unused openings shall be closed in panel, 334.30 nm cable shall be stapled within 12" of box, 314.23(A) boxes shall be securely mounted, 314.25 boxes shall have cover installed
|
Final | 12/24/2007 | 12/24/2007 | 12/24/2007 | P | NR |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig job not ready reinspection fee
|
Reinspection Fee (no hold) | 12/24/2007 | 12/24/2007 | 12/24/2007 | P | NR |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig job not ready reinspection fee
|
Permanent Service | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig p/s o/h rec ok
|
Rough-In Permanent Service | 12/20/2007 | 12/20/2007 | 12/20/2007 | P | FAIL |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig grounding to metal water pipe 5ft entring building, isolate neutral in sub panel & 2 ground rods
|
Application received | | | 12/20/2007 | | DONE |
|
|
|
This permit was created on the web by Steve Craig
|