Permit NumberELE07-04213
StatusFinaled
Name STAR VALLEY ELECTRIC
Site Address 700 N BACON DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Rough-In Permanent Service1/14/20081/14/20081/14/2008PPASS
DetailsMike Kinnear
richard Phone #: ###-#### ok ri p/s o/h reconnect ok
Final1/14/20081/14/20081/14/2008PPASS
DetailsMike Kinnear
richard Phone #: ###-#### ok final
Final12/31/20071/4/20081/4/2008AFAIL
DetailsJack Frank
richard Phone #: ###-####corr. called T310.15(B)(2)(a) derate wires 2" pvc, 312.5 cables not allowed in 2" pvc,also provide connectors for cables in back of panel, 200.6&7 shall not ID 6 or smaller, red #12 used as neutral, re ID white in 10/2 for water heater, 250.53(D)(2) needs 2 grd rods, 230.24 make sure service drop and drip loop have required clearence note remove old #8 GEC from service panel and call for r/i p/s not final
Application received  12/27/2007  
Issue permit  12/27/2007 DONE