Permanent Service | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | NR |
Jack Frank
|
|
|
dan Phone #: ###-#### needs to change or protect #8 GEC, 250.52(A !), 104(A!) shall grd within 5ft or bond water, T 220.55 shall install required size circuit for range , 314.3 needs bond bushings for metallic raceways in plastic jbox
|