Final | 5/27/2008 | 5/27/2008 | 5/27/2008 | P | PASS |
Jack Frank
|
|
|
JOE - call 1/2 for access Phone #: ###-#### ok survey gfci protection in laundry and garage , and be specific panel schedule
|
Rough-In Permanent Service | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Jack Frank
|
|
|
joe - please call 1/2 hr prior to inspection Phone #: ###-#### r/i p/s u/g new ok
|
Rough-In Permanent Service | 1/10/2008 | 1/10/2008 | 1/10/2008 | P | FAIL |
Jack Frank
|
|
|
Joe, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr met contr. 314.16 box fill, 250.148 grd all metal boxes, 210.52(A) outlet spacing upstairs, 210.11(C)(2&3) only what NEC states shall be on laundry and bath circuits, 334.23 protect cables attic access, 404.4 remove switches from tub space250.122T 14 not allowed on #12 for pigtail, 310.16T 14 not allowed on 20 amp
|
Application received | | | 12/31/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/31/2007 | | |
|
|
|
|