Second Notice ELE | 1/29/2008 | 1/29/2008 | 1/29/2008 | | DONE |
Patricia Smith
|
|
|
This permit finaled on the web by gary batten
|
First Notice | 1/11/2008 | 1/11/2008 | 1/29/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Bob Reichert
|
|
|
Tom wonnocot is the electrician @ ###-####, please provide inspection Phone #: ###-#### Internet Inspection Request from: gary batten see rip, ok to final
|
Rough-In Permanent Service | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Bob Reichert
|
|
|
Tom wonnocot is the electrician @ ###-####, please provide inspection Phone #: ###-#### Internet Inspection Request from: gary batten corrections made ric ok, p/s o/h rec ok
|
Rough-In Permanent Service | 1/7/2008 | 1/7/2008 | 1/7/2008 | P | FAIL |
Bob Reichert
|
|
|
Electrician is Tom Wonacott Phone #: ###-#### Internet Inspection Request from: Jarrod Clyme called, left correction notice, BCC no violations shall be retained, NEC 110.26 shall provide access to electrical equipment, 408.4 circuit directory shall be clear, concise and explanatory for each circuit, 406.8(B) shall use in-use cover for receptacle in wet location,334.12(B) shall not use nm cable exposed or in commercial building, 358.30 emt shall be supported within 3' of box, NOTE: Partial inspection only until access is provided reviewed with owner, told electrician bush removal might be ok for access
|
Application received | | | 1/4/2008 | | DONE |
|
|
|
This permit was created on the web by gary batten
|