ELE-Aging Inspection | 1/5/2010 | 1/5/2010 | 1/5/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 1/5/2010 | 1/5/2010 | 1/5/2010 | P | PASS |
Jack Frank
|
|
|
no activity
|
Final | 6/4/2008 | 6/5/2008 | 6/5/2008 | A | FAIL |
Jack Frank
|
|
|
Jason, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt no access talked to two different people can not get hold of electrical contr. number no good note only phone we need is the electrical contr
|
Reinspection Fee (no hold) | 6/5/2008 | 6/5/2008 | 6/5/2008 | A | DONE |
Jack Frank
|
|
|
Jason, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt fee due no access
|
Electrical Rough-In | 2/4/2008 | 2/5/2008 | 2/5/2008 | A | PASS |
Bob Reichert
|
|
|
jeremiah Phone #: ###-#### corrections made, ric ok (1 wall for bookcases)
|
Electrical Rough-In | 1/30/2008 | 1/30/2008 | 1/30/2008 | P | FAIL |
Bob Reichert
|
|
|
jeremiah - please call 1/2 hr prior to inspection Phone #: ###-#### called Hume, bad number, met owner showed what wrong, left correction notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 at least 6" free conductor measured from point in box where cable emerges shall be left for splices, BCC shall not install devices before inspection
|
Application received | | | 1/30/2008 | | |
|
|
|
|
Issue permit | | | 1/30/2008 | | DONE |
|
|
|
|