Final | 9/15/2008 | 9/16/2008 | 9/16/2008 | A | PASS |
Bob Reichert
|
|
|
jerod Phone #: ###-#### corrections made, ok to final
|
Final | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | FAIL |
Bob Reichert
|
|
|
Lars Phone #: ###-#### called, left correction notice, NEC 408.4 circuit directory shall be fully explanatory for each circuit, 410.16(C) edge of closet luninaire shall be minimum 6" from front of shelf, 406.4 laundry room receptacle shall be securely mounted, 110.3(B) listed equipment shall be installed per manufacturers instructions-upper bath receptacle show reverse polarity, other bath gfci won't set, 422.32 shall provide dishwasher circuit i.d. and disconnecting means, rest ok
|
Electrical Rough-In | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | PASS |
Jack Frank
|
|
|
jared - please call 1/2 hr prior to inspection Phone #: ###-#### all corrections made r/i p/s u/g new ok
|
Electrical Rough-In | 2/13/2008 | 2/14/2008 | 2/14/2008 | A | FAIL |
Jack Frank
|
|
|
jared - please call 1/2 hr prior to inspection Phone #: ###-#### all corrections not made amd new one created loose equip gtrds at boxes, and outside box not flush with siding
|
Reinspection Fee (no hold) | 2/14/2008 | 2/14/2008 | 2/14/2008 | A | DONE |
Jack Frank
|
|
|
jared - please call 1/2 hr prior to inspection Phone #: ###-#### fee due, all violations not corrected and new one created loose equip grds, and outside light box not flush with siding
|
Electrical Rough-In | 2/12/2008 | 2/13/2008 | 2/13/2008 | A | FAIL |
Jack Frank
|
|
|
jerod Phone #: ###-#### corr. called nail plates, crimp sleeves loose and shall use approved tool. install all outside fixture boxes, some shot equip grds free length
|
Reinspection Fee (no hold) | 2/13/2008 | 2/13/2008 | 2/13/2008 | A | DONE |
Jack Frank
|
|
|
jerod Phone #: ###-#### fee due corr
|
Electrical Rough-In | 2/1/2008 | 2/1/2008 | 2/1/2008 | P | PASS |
Bob Reichert
|
|
|
JEROD Phone #: ###-#### soffits only ok to cover
|
Application received | | | 2/1/2008 | | |
|
|
|
|
Issue permit | | | 2/1/2008 | | DONE |
|
|
|
|