Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE08-00246
StatusFinaled
Name ILLUMINATION INNOVATION
Site Address 2107 S STONYFIELD PL
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/15/20089/16/20089/16/2008APASS
DetailsBob Reichert
jerod Phone #: ###-#### corrections made, ok to final
Final9/12/20089/12/20089/12/2008PFAIL
DetailsBob Reichert
Lars Phone #: ###-#### called, left correction notice, NEC 408.4 circuit directory shall be fully explanatory for each circuit, 410.16(C) edge of closet luninaire shall be minimum 6" from front of shelf, 406.4 laundry room receptacle shall be securely mounted, 110.3(B) listed equipment shall be installed per manufacturers instructions-upper bath receptacle show reverse polarity, other bath gfci won't set, 422.32 shall provide dishwasher circuit i.d. and disconnecting means, rest ok
Electrical Rough-In2/14/20082/14/20082/14/2008PPASS
DetailsJack Frank
jared - please call 1/2 hr prior to inspection Phone #: ###-#### all corrections made r/i p/s u/g new ok
Electrical Rough-In2/13/20082/14/20082/14/2008AFAIL
DetailsJack Frank
jared - please call 1/2 hr prior to inspection Phone #: ###-#### all corrections not made amd new one created loose equip gtrds at boxes, and outside box not flush with siding
Reinspection Fee (no hold)2/14/20082/14/20082/14/2008ADONE
DetailsJack Frank
jared - please call 1/2 hr prior to inspection Phone #: ###-#### fee due, all violations not corrected and new one created loose equip grds, and outside light box not flush with siding
Electrical Rough-In2/12/20082/13/20082/13/2008AFAIL
DetailsJack Frank
jerod Phone #: ###-#### corr. called nail plates, crimp sleeves loose and shall use approved tool. install all outside fixture boxes, some shot equip grds free length
Reinspection Fee (no hold)2/13/20082/13/20082/13/2008ADONE
DetailsJack Frank
jerod Phone #: ###-#### fee due corr
Electrical Rough-In2/1/20082/1/20082/1/2008PPASS
DetailsBob Reichert
JEROD Phone #: ###-#### soffits only ok to cover
Application received  2/1/2008  
Issue permit  2/1/2008 DONE