First Notice | 4/26/2012 | 4/26/2012 | 3/19/2013 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Sean DeLacy
|
Final | 4/25/2012 | 4/26/2012 | 4/26/2012 | A | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok final
|
Final | 4/23/2012 | 4/25/2012 | 4/25/2012 | A | NH |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, no access
|
ELE-Aging Inspection | 3/19/2012 | 3/19/2012 | 3/21/2012 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Final | 12/19/2011 | 12/20/2011 | 12/20/2011 | A | FAIL |
Bob Reichert
|
|
|
Sean. Please call prior to heading to site. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy corrections not made
|
Final | 11/10/2011 | 11/14/2011 | 11/14/2011 | A | FAIL |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 110.12(A) shall close unused openings, 258.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
|
Final | 11/3/2011 | 11/4/2011 | 11/4/2011 | P | NR |
Bob Reichert
|
|
|
Jason Phone #: ###-#### >> Inspection requested via web by Sean DeLacy still working basement
|
Final | 11/3/2011 | 11/3/2011 | 11/3/2011 | P | CANC |
Bob Reichert
|
|
|
Jason Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
ELE-Aging Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
ELE-Aging Inspection | 7/7/2011 | 7/7/2011 | 7/7/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Permanent Service | 4/7/2011 | 4/7/2011 | 4/7/2011 | A | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy p/s u/g n ok, 2 meters
|
Rough-In Permanent Service | 4/5/2011 | 4/5/2011 | 4/5/2011 | P | NR |
Bob Reichert
|
|
|
Scott Phone #: ###-#### >> Inspection requested via web by Sean DeLacy need to change grounding
|
ELE-Aging Inspection | 3/28/2011 | 3/28/2011 | 3/28/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Change Status to I | | | 3/25/2011 | | DONE |
Tisha Gallop
|
|
|
per Doug Poedy ok to reopen permit, 2 hr admin fee
|
Telephone call | | | 3/24/2011 | | DONE |
Tisha Gallop
|
|
|
called Sean Delacey/RME electric, left vm to reopen expired permits Ele07-03492, Ele08-00318, each would be two hr admin fee of $92.62 fee needs to be paid to reopen permits.
|
Case Summary (ELE) | | | 3/16/2010 | | DONE |
|
|
|
|
ELE-Aging Inspection | 6/18/2009 | 6/18/2009 | 6/22/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 6/22/2009 | 6/22/2009 | 6/22/2009 | P | PASS |
Jack Frank
|
|
|
already had 3 aging and still no action
|
ELE-Aging Inspection | 4/15/2009 | 4/15/2009 | 4/16/2009 | | DONE |
Bob Reichert
|
|
|
suc, no activity
|
ELE-Aging Inspection | 2/13/2009 | 2/13/2009 | 2/13/2009 | | DONE |
Bob Reichert
|
|
|
project suc
|
ELE-Aging Inspection | 12/9/2008 | 12/9/2008 | 12/9/2008 | | DONE |
Bob Reichert
|
|
|
suc
|
Electrical Rough-In | 4/9/2008 | 4/10/2008 | 4/10/2008 | A | PART |
Pat Lass
|
|
|
TOBY DECK INSPECTION Phone #: ###-#### Internet Inspection Request from: Sean DeLacy slab ok
|
Electrical Rough-In | 3/24/2008 | 3/25/2008 | 3/25/2008 | A | PASS |
Bob Reichert
|
|
|
UFFER GROUND MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok for concrete encased electrode, using clamp approved for concrete encasement
|
Electrical Rough-In | 2/8/2008 | 2/11/2008 | 2/11/2008 | A | PART |
Bob Reichert
|
|
|
MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to pour north part slab, anop, west unit
|
Application received | | | 2/8/2008 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|