Electrical Rough-In | 3/3/2008 | 3/4/2008 | 3/4/2008 | A | PASS |
Jack Frank
|
|
|
jack all issues have been corrected. thanks bob Phone #: ###-#### Internet Inspection Request from: robert tomlinson ok
|
Final | 3/4/2008 | 3/4/2008 | 3/4/2008 | A | PASS |
Jack Frank
|
|
|
jack all issues have been corrected. thanks bob Phone #: ###-#### Internet Inspection Request from: robert tomlinson p/s u/g new ok
|
Rough-In Permanent Service | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | FAIL |
Jack Frank
|
|
|
bob - also the kitchen and garage Phone #: ###-#### called corr posted 300.4 nail plates and 11/4", 314.16 box fill, 300.14 6" free length, 250.148 slpice all equip grds together at boxes, 250.52(A)(1) grd water within 5ft of metal u/g water pipe from service not sub panel312.5 (C) exception pvc shall exit top of panel
|
Reinspection Fee (no hold) | 2/28/2008 | 2/28/2008 | 2/28/2008 | A | DONE |
Jack Frank
|
|
|
bob - also the kitchen and garage Phone #: ###-#### fee due, correction
|
Application received | | | 2/8/2008 | | |
|
|
|
|
Issue & PRINT permit | | | 2/8/2008 | | DONE |
|
|
|
|