Permanent Service | 2/19/2008 | 2/20/2008 | 2/20/2008 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/19/2008 at 1:00:58 PM. Contact: ###-####. p/s o/h rec. ok
|
Final | 2/20/2008 | 2/20/2008 | 2/20/2008 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/19/2008 at 1:00:58 PM. Contact: ###-####. ok
|
Permanent Service | 2/19/2008 | 2/19/2008 | 2/19/2008 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/19/2008 at 7:44:55 AM. Contact: ###-####. called contractor, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 352.30 rnc shall be strapped within 3' of panel, 408.4 shall complete panel schedule, BCC no violations shall be retained
|
Permanent Service | 2/13/2008 | 2/14/2008 | 2/14/2008 | A | NR |
Mike Kinnear
|
|
|
aaron Phone #: ###-#### t/w aaron & john they get grounding up to code & another life safety issues then call for p/s inspection
|
Application received | | | 2/13/2008 | | |
|
|
|
|
Issue permit | | | 2/13/2008 | | DONE |
|
|
|
|