Final | 3/20/2008 | 3/25/2008 | 3/25/2008 | P | PASS |
Jack Frank
|
|
|
re-inspection Phone #: ###-#### Internet Inspection Request from: Yolanda Morris ok
|
Electrical Rough-In | 3/10/2008 | 3/13/2008 | 3/13/2008 | P | FAIL |
Jack Frank
|
|
|
reinspect final electrical rough in Phone #: ###-#### Internet Inspection Request from: Yolanda Morris corr not still needs manufactures listed breakers called
|
Reinspection Fee (no hold) | 3/13/2008 | 3/13/2008 | 3/13/2008 | P | DONE |
Jack Frank
|
|
|
reinspect final electrical rough in Phone #: ###-#### Internet Inspection Request from: Yolanda Morris fee due all violations not made
|
Final | 2/25/2008 | 2/28/2008 | 2/28/2008 | P | CANC |
Jack Frank
|
|
|
PLEASE CALL BEFORE YOU SHOW, MR. WILLIAM BRYANT ###-#### OR ###-#### CELL Phone #: ###-#### Internet Inspection Request from: Angela Parker see r/i request
|
Electrical Rough-In | 2/28/2008 | 2/29/2008 | 2/28/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corr called300.10&12 tighten all locknuts, 110.3(B) use only manufactures listed breakers, and 20 amp max breaker for a/c, 312.5(C) romex not allowed in concuit, unless done as code noted states, 408.7 seal unused breaker openings
|
Application received | | | 2/22/2008 | | DONE |
|
|
|
This permit was created on the web by Angela Parker
|