Second Notice ELE | 3/3/2009 | 3/3/2009 | 12/12/2011 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by Zane Robertson
|
Second Notice ELE | 3/3/2009 | 3/3/2009 | 12/12/2011 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by Zane Robertson
|
First Notice | 9/18/2008 | 9/18/2008 | 3/3/2009 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 9/18/2008 | 9/18/2008 | 3/3/2009 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/17/2008 | 9/18/2008 | 9/18/2008 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/17/2008 at 8:08:27 AM. Contact: ###-####. corrections made, ok to final, signed occupancy card, could not add esc comments
|
Final | 9/15/2008 | 9/15/2008 | 9/15/2008 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/15/2008 at 8:18:41 AM. Contact: ###-####. called, left correction notice, NEC 330.30(A)&(B) approved securing devices shall be used and mc shall be secured within 12" of cable termination, 300.11(A) support wires shall provide secure support and be secured at both ends, BCC all work shall be completed, (front counter)
|
Final | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 9/12/2008 at 10:24:32 AM. Contact: ###-####. wrong type inspection
|
Conference | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | DONE |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 9/12/2008 at 10:24:32 AM. Contact: ###-####. drop ceiling support needs to be id., use listed supports, 12inch from boxes, & 6ft when dasey chained, wire needs to be connected from ceiling & grid.
|
Permanent Service | 8/20/2008 | 8/21/2008 | 8/21/2008 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/20/2008 at 3:05:10 PM. Contact: ###-####. talked to contr, at time of final accessibility to breaker shall meet NEC 240.24 p/s u/g new ok
|
Permanent Service | 8/19/2008 | 8/20/2008 | 8/20/2008 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/19/2008 at 11:47:47 AM. Contact: ###-####. called, left correction notice, NEC 404.8 center of grip of operating handle shall not be over 6'-7" above floor, 110.22 disconnects shall be labelled to indicate its purpose and be of sufficient durability to withstand its environment, 250.68 connection to grounding electrode shall be accessible, 358.30(A) shall strap emt within 3' of box,250.52 shall provide concrete encased electrode, BCC shall provide separate electrical permit for 2nd meter
|
Electrical Rough-In | 8/12/2008 | 8/12/2008 | 8/12/2008 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/12/2008 at 9:38:44 AM. Contact: ###-####. ok to cover ceilings part lobby, conference, and shower rooms
|
Electrical Rough-In | 8/7/2008 | 8/7/2008 | 8/7/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/7/2008 at 8:28:53 AM. Contact: ###-####. hard lids for halls and baths ok to cover
|
Electrical Rough-In | 7/29/2008 | 7/29/2008 | 7/29/2008 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 7/29/2008 at 10:36:53 AM. Contact: ###-####. ok cover under ground conduit for site lighting in front of building
|
Electrical Rough-In | 7/28/2008 | 7/28/2008 | 7/28/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/28/2008 at 8:53:55 AM. Contact: ###-####. walls only ok to cover except warehouse area
|
Electrical Rough-In | 7/24/2008 | 7/25/2008 | 7/25/2008 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/24/2008 at 11:43:22 AM. Contact: ###-####. called contractor, left correction notice, NEC 300.4 where subject to physical damage, shall protect cables if not 1 1/4" from face of framing members,BCC Shall complete all work before inspection, shall not use valley of steel studs to secure cable, shall have address posted
|
Electrical Rough-In | 4/14/2008 | 4/14/2008 | 4/14/2008 | P | PART |
Bob Reichert
|
|
|
zane Phone #: ###-#### called contractor - north side of property line u/g for area lighting only ok to cover, under parking lot driveway entrance not deep enough, contractor will check and recall
|
Electrical Rough-In | 3/21/2008 | 3/21/2008 | 3/21/2008 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 3/21/2008 at 7:00:54 AM. Contact: ###-####. ok cover under slab conduit only
|
Electrical Rough-In | 3/6/2008 | 3/7/2008 | 3/7/2008 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/6/2008 at 2:51:08 PM. Contact: ###-####. ok to pour under slab only, called contractor to ensure sand bedding for raceways
|
Conference | 2/27/2008 | 2/28/2008 | 2/27/2008 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/27/2008 at 1:46:29 PM. Contact: ###-####. Inspection cancelled from web by: Patricia Smith
|
Application received | | | 2/25/2008 | | |
|
|
|
|
Issue permit | | | 2/25/2008 | | DONE |
|
|
|
|