Second Notice ELE | 7/14/2008 | 7/14/2008 | 7/15/2008 | | DONE |
Patricia Smith
|
|
|
This permit finaled on the web by Barbara Szurgot
|
First Notice | 6/20/2008 | 6/20/2008 | 7/14/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 6/19/2008 | 6/20/2008 | 6/20/2008 | A | PASS |
Bob Reichert
|
|
|
If not open, key is at Suite A100 Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corrections made, ok to final, signed occupancy card, no ecs this project
|
Final | 6/18/2008 | 6/18/2008 | 6/18/2008 | P | FAIL |
Bob Reichert
|
|
|
If not unlocked, there is a key at Suite A100. Thanks Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called, left correction notice, BCC no violations shall be retained, approved set of plans shall be on job,NEC 330.40 mc cable shall be connected with approved fittings, 330.24(B) mc cable shall be connected within 12 of termination, 348.30(A) fmc shall be secured within 12" of termination, 358.30(A) emt shall be secured within 3' of termination,406.4 receptacles shall be rigidly mounted and covers installed, 110.22 disconnects shall be labelled and marked, no esc
|
Final | 6/18/2008 | 6/18/2008 | 6/18/2008 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
|
Electrical Rough-In | 3/13/2008 | 3/14/2008 | 3/14/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok cover ri
|
Application received | | | 3/12/2008 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|