ELE-Aging Inspection | 6/8/2010 | 6/8/2010 | 6/8/2010 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 6/8/2010 | 6/8/2010 | 6/8/2010 | A | PASS |
Bob Reichert
|
|
|
no activity
|
ELE-Aging Inspection | 4/8/2010 | 4/8/2010 | 4/16/2010 | | CANC |
Bob Reichert
|
|
|
wrong permit responded to
|
Rough-In Permanent Service | 6/19/2008 | 6/19/2008 | 6/19/2008 | P | FAIL |
Pat Lass
|
|
|
james Phone #: ###-#### 6 in free conductor at all boxes no permit no violations to be retained and proper connectors required on romex
|
Permanent Service | 6/18/2008 | 6/19/2008 | 6/19/2008 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA P/S O/H R Ok
|
Final | 4/30/2008 | 5/1/2008 | 5/1/2008 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA uncover work done prior to permit being taken out insure correct room count add service to permit. 2" imc or ridged required for mast support, bond raceway between meter and panel, GEC not permited in metal raceway without bonding both ends, and cable to enter through proper fittings
|
Permanent Service | 4/29/2008 | 4/30/2008 | 4/30/2008 | A | FAIL |
William E Thomas
|
|
|
service grounding inspection Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA . .1. no access to the panel. . .
|
Application received | | | 3/19/2008 | | DONE |
|
|
|
This permit was created on the web by HARVEY REYNA
|