Final | 4/23/2008 | 4/25/2008 | 4/25/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jenni Keller ok
|
Electrical Rough-In | 4/17/2008 | 4/21/2008 | 4/21/2008 | A | FAIL |
Jack Frank
|
|
|
220v Spa Connection Phone #: ###-#### Internet Inspection Request from: Jenni Keller 110.3(A) replace damaged conductors at terminals ringed the wires, 352.26&356.26 over 360degrees of bends in PVC &LFNC, 356.1 &42 use listed fittings for LFNC not allowed to be glued to PVC coupling, 680.26(A)(5) bond all mwtal around spa as code noted states, check if PVC is schedule 80 called
|
Reinspection Fee (no hold) | 4/21/2008 | 4/21/2008 | 4/21/2008 | P | DONE |
Jack Frank
|
|
|
220v Spa Connection Phone #: ###-#### Internet Inspection Request from: Jenni Keller fee due corr posted
|
Application received | | | 4/17/2008 | | DONE |
|
|
|