Second Notice ELE | 3/3/2009 | 3/3/2009 | 3/6/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
First Notice has not been responded to.
|
First Notice | 8/6/2008 | 8/6/2008 | 3/3/2009 | | DONE |
Bob Reichert
|
|
|
|
Final | 8/5/2008 | 8/6/2008 | 8/6/2008 | A | PASS |
Bob Reichert
|
|
|
danny - working nights - can you come early? Phone #: ###-#### ok to final, signed structural card
|
Final | 7/29/2008 | 7/30/2008 | 7/30/2008 | A | PART |
Bob Reichert
|
|
|
danny Phone #: ###-#### part of store anop ok to final, roof, a/h unit room, elect room, storage area, deli, bakery, will see rest of ceilings later
|
Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 | A | FAIL |
Bob Reichert
|
|
|
danny Phone #: ###-#### met electrician, left correction notice, BCC no violations shall be retained, no lv shall be on tiles or grid,NEC 725.8 class 1,2,3 cables shall be supported by building structure with straps, hangars, or similar fittings and installed so as to not damage the cable and also conform to article 300.4(D), 400.8(5) cord shall not be concealed by ceilings or above dropped ceilings
|
Electrical Rough-In | 7/16/2008 | 7/17/2008 | 7/17/2008 | A | CANC |
Bob Reichert
|
|
|
Bud- ceiling Phone #: ###-#### wrong type inspection, see part final
|
Final | 7/17/2008 | 7/17/2008 | 7/17/2008 | A | PART |
Bob Reichert
|
|
|
Bud- ceiling Phone #: ###-#### ok to part final ceiling anop
|
Electrical Rough-In | 7/16/2008 | 7/16/2008 | 7/16/2008 | A | CANC |
Bob Reichert
|
|
|
bud Phone #: ###-####, wrong type request, see part final
|
Final | 7/16/2008 | 7/16/2008 | 7/16/2008 | P | PART |
Bob Reichert
|
|
|
bud Phone #: ###-#### reviewed part ceiling, ok to final west part anop
|
Electrical Rough-In | 7/9/2008 | 7/9/2008 | 7/9/2008 | P | PASS |
Bob Reichert
|
|
|
DANNY Phone #: ###-#### walls only deli anop ok to cover
|
Electrical Rough-In | 7/7/2008 | 7/8/2008 | 7/8/2008 | A | CANC |
Bob Reichert
|
|
|
Danny Phone #: ###-#### contractor calle d to cancel for today
|
Electrical Rough-In | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | PART |
Bob Reichert
|
|
|
DANNY Phone #: ###-#### ok to cover u/g and soffit anop, partial final for nw electrical in customer service, office area, electric and hvac rooms, left correction notice for roof which didn't see BCC no violations shall be retained- such as disconnects for roof-top units- this adds to correction notice of 7-2-08
|
Electrical Rough-In | 7/1/2008 | 7/2/2008 | 7/2/2008 | A | PART |
Bob Reichert
|
|
|
Danny- ceiling Phone #: ###-#### ok to cover ceiling anop, west part building, northwest part ok to final this part, left correction notice to owner and the electrical permit. BCC no violations shall be retained-such as no lv wiring shall be on tiles or grid, conduits shall be supported, boxes closed, abandoned circuits closed,i.e. no live wiring exposed
|
Electrical Rough-In | 6/25/2008 | 6/26/2008 | 6/26/2008 | A | PART |
Bob Reichert
|
|
|
danny Phone #: ###-#### u/g ok to cover anop, take-n-bake area ok to final anop
|
Electrical Rough-In | 6/12/2008 | 6/17/2008 | 6/17/2008 | A | PART |
Bob Reichert
|
|
|
Danny, this is for underground; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt u/g north east part store ok to cover, anop
|
Electrical Rough-In | 6/12/2008 | 6/13/2008 | 6/13/2008 | A | PASS |
Bob Reichert
|
|
|
Danny; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling in take-n-bake area anop only
|
Electrical Rough-In | 6/10/2008 | 6/11/2008 | 6/11/2008 | A | PASS |
Bob Reichert
|
|
|
danny Phone #: ###-#### walls only anop ok to cover
|
Electrical Rough-In | 6/5/2008 | 6/6/2008 | 6/6/2008 | A | PASS |
Bob Reichert
|
|
|
Danny Phone #: ###-#### ok to cover walls anop (pizza area)
|
Final | 6/5/2008 | 6/6/2008 | 6/5/2008 | A | CANC |
Bob Reichert
|
|
|
Danny Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
|
Electrical Rough-In | 5/28/2008 | 5/29/2008 | 5/29/2008 | A | PART |
Bob Reichert
|
|
|
danny - underground Phone #: ###-#### ok to cover u/g for take-n-bake pizzeria area only in front of check-outs anop, also marked on plans for floral area
|
Electrical Rough-In | 5/27/2008 | 5/28/2008 | 5/28/2008 | A | PART |
Bob Reichert
|
|
|
danny Note: underground Phone #: ###-#### met contractor, ok to cover u/g and wall only by floral at west entrance. Told must have set of prints for next inspection to mark on. Told again that no violations shall be retained.
|
Electrical Rough-In | 5/8/2008 | 5/8/2008 | 5/8/2008 | P | PART |
Bob Reichert
|
|
|
danny Note: underground Phone #: ###-#### ok to cover u/g column E-3 only
|
Electrical Rough-In | 5/2/2008 | 5/5/2008 | 5/5/2008 | A | PART |
Bob Reichert
|
|
|
danny - ok to cover Phone #: ###-#### phase 1 wall only ok to cover, told contractor to get set of prints we will mark on
|
Application received | | | 4/23/2008 | | DONE |
|
|
|